85162 Murr Elektronik MCS-B Power Supply 1 Phase (New)
INPUT
Input voltage | 95…265 V AC; 110…300 V DC |
---|---|
Input current | 1.04 A (110 V AC); 0.63 A (230 V AC) |
Inrush current after 1 ms | max. 20 A |
Primary fusing external | max. 10 A |
Frequency | 50…60 Hz |
GENERAL DATA
Standards | EN 60950-1, EN 61204-3, EN 55022 B, EN 61000-3-2 |
---|---|
Relative humidity | 5…95%, no condensation |
Efficiency | 85% (110 V AC); 87% (230 V AC) |
Dimensions H × W × D | 76×38×108 mm |
Mounting method | DIN-rail mountable TH35 (EN 60715) |
Temperature range | -25…+40 °C, …+50 °C derating (storage temperature -25…+85 °C) |
OUTPUT
Output voltage | 24 V DC (SELV), ±1%; 22…28 V adjustable |
---|---|
Output current | 2.5 A (+40 °C); 2.0 A (+55 °C) |
Mains failure bridging time | min. 15 ms (110 V AC); min. 80 ms (230 V AC) |
Ripple | max. 50 mVrms |
Spikes | max. 120 mV p-p |
Unit protection | short-circuit and overload protected |
LED display | LED (green) for output voltage |
Parallel usage/serial usage | max. 5 units/max. 2 units |