Technical Details PNOZ X3
Electrical Data
Supply Voltage AC: 24, 42, 48, 110, 115, 120, 230, 240 V
DC: 24 V
Tolerance 85 … 110 %
Power Consumption Approx.2.5 W/5 VA
Voltage and Current at the Input and 24 VDC, 35 mA
Reset Circuits and Feedback Control Loop
Switching Capability in accordance with
EN 60947-4-1, 10/91 AC1: 240 V/8 A/2000 VA
DC1: 24 V/8 A/200 W
EN 60947-5-1, 10/91 AC15: 230 V/5 A; DC13: 24 V/6A
(DC13: 6 cycles/min.)
Output Contacts 3 safety contacts (N/O),
1 auxiliary contact (N/C)
Contact Fuse Protection 10 A quick or 6 A slow
(EN 60947-5-1, 10/91)
Semiconductor Outputs 24 VDC/20 mA, short-circuit protected
External Supply Voltage 24 VDC Ā±20 %
Times
Delay-on Energisation Monitored manual reset: max. 100 ms
Auto./ manual reset: max. 0.3 s
Delay-on De-energisation With E-STOP: max. 80 ms
With power failure: max. 1 s
Recovery Time Approx. 1 s
Simultaneity channel 1/2
Max. Supply Interruption before De-energisation Approx. 25 ms
Environmental Data
Ambient Temperature -25 … +55 Ā°C
Mechanical Data
Maximum Cross Section of 2 x 1.5 mm2 or 1 x 2.5 mm2
External Conductors Single-core or multi-core
with crimp connectors
Dimensions (H x W x D) 87 x 45 x 121 mm
Weight 420 g